LK Automation Limited LK Automation Limited
Download Sort: OMRON
Home >> Catalog Download
OMRON G3S4 Series datasheet PDF catalog G3S4 Series PDF datasheet
Product model: G3S4 Series
Name: Terminal SSR
Brand: OMRON
Sort: PDF datasheet
File language: English
Number of phases: Three-phase.
Insulation method: Phototriac coupler.
Operation indicator: Yes (yellow).
Rated input voltage: 12 to 24 VDC.
Zero cross function: Yes.
Type: Externally attached heat sinks.
Applicable load: 25 A, 200 to 480 VAC.
Number of pole: 2.
Compact, Slim-profile SSRs with Heat Sinks G3S4 Series PDF datasheet.
Solid State Contactors for Three-phase.
Heaters Reduced Installation Work G3S4 Series
with DIN Track Mounting.
RoHS compliant.
Surge pass protection improved surge dielectric strength,
for output currents. (OMRON testing).
Slim design with 3-phase output and built-in heat sinks.
DIN Track mounting types and screw mounting types are available.
All DIN Track mounting types mount to DIN Track G3S4 Series PDF datasheet.
(applicable DIN Track: TR35-15Fe (IEC 60715)).
Conforms to UL, CSA, and EN standards (TÜV certification). Standard certification: No.
Action indicator: there.
Applicable load of output: DC4 3A ~ 48V.
Input rated voltage: DC5 ~ 24V.
Insulation: photo coupler.
Zero trigger function: No.
And the MY type of the same shape of the G3F series of new international standard certification (-VD type) G3S4 Series PDF datasheet.
Achieved UL, CSA, EN (VDE certification) standard certification. (type -VD)
Socket terminal type of same size with MY (2 pole type).
A model with an action indicator to check the status of the input. Input capacity: 32 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided foor,
each connector G3S4 Series datasheet PDF catalog.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software G3S4 Series datasheet PDF catalog.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.