Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC) GLS-1 PDF datasheet.
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0
GLS-15 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max GLS-1 PDF datasheet.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors GLS-1 PDF datasheet.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Type: output module.
Insulation: photo coupler.
Zero crossing function.
Action display lamp.
Output rated voltage: AC100 3A ~ 240V.
Input rated voltage: DC5 ~ 24V.
Logic circuit and load interface.
I/O solid state relay.
With the input module (AC, DC), the output module (AC, DC).
Product series, the color of each module to distinguish.
You can confirm the action of SSR by using the action display light.
Between input and output voltage 4000V. Isolation: Photocoupler.
Zero cross function: Yes.
Indicator: Yes(Yellow).
Applicable output load (See note 1.): 40 A at 24 to 240 VAC(See note 2.).
Rated input voltage: 200 to 240 VAC.
Wide Lineup of General-purpose Solid State.
Relays with Applicable Loads of 5 to 90 A.
AC Output Relays with 75-A and 90-A output currents have been,
added to the G3NA Series. GLS-1 datasheet PDF catalog.
All models feature the same compact dimensions to provide a,
uniform mounting pitch.
Built-in varistor effectively absorbs external surges.
(except G3NA-D210B).
Operation indicator enables monitoring operation.
Prrotective cover for greater safety GLS-1 datasheet PDF catalog.
Standard models certified by UL and CSA and -UTU models by TÜV.
(except G3NA-410B, G3NA-420B, and G3NA-440B(-2)).