Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC) G9SX-AD322-T15-RT USER'S MANUAL.
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0
G9SX-AD322-T15-RT5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max G9SX-AD322-T15-RT USER'S MANUAL.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors G9SX-AD322-T15-RT USER'S MANUAL.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Mounting type: W-bracket(see note).
Contact form: 4PST-NO.
Quick-connect terminals.
A High-capacity, High-dielectric-strength,
Multi-pole Relay Used Like a Contactor.
Miniature hinge for maximum switching power for motor loads,
as well as resistive and inductive loads G9SX-AD322-T15-RT Manual.
No contact chattering for momentary voltage drops up to 50%,
of rated voltage.
Withstanding more than 4 kV between contacts that are differ,
ent in polarity and betweenn the coil and contacts G9SX-AD322-T15-RT Manual.
Flame-resistant materials (UL94V-0-qualifying) used for all in,
sulation material.
Standard models approved by UL and CSA.