OMRON GRT1-DRT Manual GRT1-DRT REFERENCE MANUAL
Product model: GRT1-DRT
Name: Motion Control Unit
Brand: OMRON
Sort: REFERENCE MANUAL
File language: English
Insulation method: Photocoupler.
Operation indicator: Yes.
Response speed: Low-speed.
Applicable load: 4 to 32 VDC 0.1 to 100 mA.
Input rated voltage: 12 to 24 VDC.
SSR with Plug-in Terminals.
The Same Shape as the G2R-1-S.
Power Relays.
These I/O solid state relays can be mounted in OMRON.
G70A I/O Terminals GRT1-DRT REFERENCE MANUAL.
Lineup includes Input Modules for microloads and Output,
Modules for standard loads GRT1-DRT
Lineup also includes UL, CSA, and TÜV-certified models,
(-UTU models). Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
(between each input terminal and the G terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the G terminal)
OFF current: 1.0 mA max GRT1-DRT REFERENCE MANUAL.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms. (Default setting: 1 ms)
Number of circuits per common: 8 points/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply GRT1-DRT REFERENCE MANUAL.
Input device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance. Name: CompoNet Gateway Unit for CC-Link.
Specifications: CC-Link Communications,
Specification, Station Type,
Remote device stations;
Number of stations occupied: 4.
CC-Link Version: Version 1.10 or 2.00.
(Selected using mode switch.);
CompoNet Communications Specification,
communications Types of,
Remote I/O Communications;
Maximum I/O capacit, Word Slave Units:
2,048 I/O points total(1,024 inputs and,
1,024 outputs)Bit Slave Units:
512 I/O points total.
(256 inputs and 256 outputs)
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material costt can be reduced GRT1-DRT Manual.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on sitee GRT1-DRT Manual.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.
Related products
OMRON
CompoNet Communications Unit
GRT1-ID4-1
OMRON CompoNet Communications Unit GRT1-ID4-1
Name: Slice I/O Units Digital I/O Units
OMRON
CompoNet Communications Unit
GRT1-OD4-1
OMRON CompoNet Communications Unit GRT1-OD4-1
Name: Slice I/O Units Digital I/O Units
OMRON
Digital Sensor Communication Unit
E3X-DRT21-S VER.3
OMRON Digital Sensor Communication Unit E3X-DRT21-S VER.3
Type: Device Net. The DeviceNet Communi