Output: DPDT.
Lighting: LED (with built-in reduced-voltage lighting function).
Operating voltage: 200/220 VAC/VDC.
Pushbutton colorsymbol: R: red, Y: yellow; PY: pure yellow
G: green, A: blue; PW: pure white; B: black *2.
Item: Alternate operation (Self-holding).
Separate Construction with.
Cylindrical 16-dia. Body.
Miniature design of 28.5 mm, the smallest class in the industry.
Detachable Switch
A22RL-TY-6A-20A
The same contacts can be used for both standard loads and microloads.
Easy-to-wire terminal arrangement.
Certified for EN 60947-5-1. Slim Safety Door Switches with IP67 Rating.
Slim design with a width of only 17 mm.
(three-contact models).
Reversible design allowing either front or rear mounting.
Built-in Switches with two- or three-terminal contact.
construction are available.
Operation Key with rubber mounting hole to absorb vibration and shock.
IP67 degree of protection. Terminal type: Exposed-lead Models.
Protective tubing diameter D (mm): 1.6 dia.
Protective tubing length L: 20cm.
Lead wire type: Standard.
Lead wire length M : 1m.
A Wide Variety of High-precision.
Temperature Sensors.
Previous models with M3 screw connections have been joined,
by new models with ferrules to help reduce wiring work.
Ideal for the thermal input devices of Temperature Controllers.
Select from a wide variety of Temperature Sensors according,
to the temperature to be measured, location, and environment,
and also according to the type and shape of the terminal. Unit classification: CJ1 Special I/O Units.
Product name: Process Input Units,
(Isolated type Units with Universal Inputs).
Input points: 4 inputs.
Signal range selection:
Set separately for each input.
Signal range:Fully universal
inputs: Pt100, JPt100, Pt1000, K,
J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA,
1 to 5 V, 0 to 5 V, 0 to 10 V.
Conversion speed (resolution): Conversion,
speed: 250 ms/4 inputs.
Accuracy at ambient temperature of 25°C:
Accuracy: Platinum resistance thermometer,
input: ±0.3% of PV or ±0.8°C, whichever,
is larger) ±1 digit max. Thermocouple input:
(±0.3% of PV or ±1.5°C, whichever is larger),
±1 digit max. *1 Voltage or current input:
±0.3% of F.S. ±1 digit max.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.32A; 24V, --.
Standards: UC1, L, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e.g., 4 to 20 mA or 1 to 5V).
A Unit supports four input channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage).
All inputs are isolated.
A22RL-TY-6A-20A Operation manual/Instructions/Model selection sample download link:
/searchDownload.html?Search=A22RL-TY-6A-20A&select=5