Name: Basic Unit(gradient temperature control)(See note 1.).
Power supply voltage: 24 VDC supplied from the End Unit.
No. of control points: 4.
Control outputs 1 and 2: Voltage output: 2 points (for SSR drive)(See note 2.).
Control outputs 3 and 4: Voltage output: 2 points (for SSR drive) (See note 2.).
Auxiliary output: None.
Functions: Heater burnout alarm, None; Event inputs, None.
Communications functions: G3ZA connection port,
RS-485 From End Unit, Port A, RS-485
ZS-LD80 1M
Input type: Thermocouple, platinum resistance thermometer,
analog voltage, and analog current selectable for each channel.
Terminal: M3 terminal.
Gradient Temperature Control to Achieve.
Consistent Layer Temperature.
Perform gradient temperature control ranging from 2 to 32 channels.
Perform 2-channel gradient temperature control for up to 16,
groups, or 32-channel gradient temperature control for up to 2 groups.
Set gradient temperature control or 2-PID control for each group.
Reduce design work for ladder programming with programless,
connections to Programmable Controllers. (The same feature,
as Standard-control EJ1 Models.).
Connect directly to the G3ZA Multi-channel Power Controller,
using optimum cycle control for high-accuracy control with minimal noise. MK-S-series Relays with DC-switching,
Models That Can Switch 220 VDC, 10 A,
(Resistive Load).
Switch a DC load of 220 VDC, 10 A (resistive load).
Models for AC Loads can switch 250 VAC, 15 A (resistive load).
Lineup includes models with SPST-NO and SPST-NO/SPST,
NC contact forms.
Using a SPST-NO/SPST-NC contact form enables detecting,
contact welding. (When the NO contacts become welded, the,
NC contacts will maintain a minimum distance of 0.5 mm.).
Models available with operation indicators and built-in test buttons.
RoHS compliant.
Standards: UL, IEC (TÜV certification). Size: 48 x 96mm.
Type: power AC/DC24V with.
Shell color: black.
Control output 1: position ratio with relay output.
Control output 2: position ratio with relay output.
Control mode: position ratio control.
Auxiliary output points: 2 points.
Event entry point: 4.
Transfer output: transfer output (special terminal).
Remote SP:4 to 20mA input.
Communication: -.
General thermostat new high performance (high resolution, high speed, high precision input) type products.
Support simple operation, preventive maintenance.
A new type of liquid crystal, which can communicate with the front through the infrared port, is adopted,
Visual angle, contrast can be improved.
High resolution 5 bit display / can display 0.01 degrees C.
High speed sampling period 60ms.
All models complete a variety of (to the thermocouple /Pt/ analog input switching), 1 machines to support a variety of sensors.
Also supports remote SP.
Add PV/SV status display function, convenient to check the state of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactive display PV/SV.
By supporting software (Ver.4.0 CX-Thermo) to carry out a simple function (AND/OR logic and delay),
Be able to execute flexible contact output.
Increase the control output ON/OFF number counting function, can predict the temperature controller internal relay fault.
Position ratio type.
ZS-LD80 1M Operation manual/Instructions/Model selection sample download link:
/searchDownload.html?Search=ZS-LD80 1M&select=5