Specifications: Outputs; NPN (- common); 16 points.
I/O connections: M3 Screw terminals.
Supplied from the communications connector.
Rated I/O power supply voltage: 24 VDC.
Allows I/O Expansion with Transistor Terminals.
of the control system.
on the communications power supply.
and equipment operating information.
Expansion via Expansion I/O Units.
maintenance is easier.
Input capacity: 16 points.
Rated current (ON current): 0.5 A/output,
4.0 A/common.
Internal I/O common: PNP.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the V terminal)
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common:
8 points/common OMRON DRT2-OD16.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation
DRT2-OD16
I/O power supply method: Supply by I/O power supply.
Output device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max OMRON DRT2-OD16.
Expansion functions: No.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance OMRON DRT2-OD16.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance. Name: System Units; I/O Power Feed Unit.
Specifications: Use when the total current,
consumption of the I/O Power Supply exceeds 4 A,
or to make the I/O Power Supply a separate system.
Standards: CE, UC, L.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring materiial cost can be reduced DRT2-OD16.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on sitee DRT2-OD16.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.