Specifications: Outputs, PNP (+ common), 32 outputs.
I/O connections: MIL connector.
Supplied from communications connector.
Rated I/O power supply voltage: 24 VDC.
and eliminates much on-site wiring.
User boards attach easily to the DRT2-@D32BV(-1) using screws.
Name: Three-tier Screw Terminal Block.
Specifications: Inputs; 8 inputs; PNP;
With Short-circuit and,
Disconnected Line Detection.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system OMRON DRT2-OD32B-1.
A wide variety of CompoNet Slave Units,
contribute to system size reduction
DRT2-OD32B-1
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. I/O classification: Input.
Internal I/O circuit common: NPN (+ common) OMRON DRT2-OD32B-1.
I/O points: 16.
Rated voltage: 24 VDC.
I/O rated voltage: 24 VDC.
Module Type that Allows PCB Mounting.
Compact size at 60 x 16 x 35 (W x H x D).
Lineup now includes the 16-point input model and,
16-point output model. Input capacity: 16 points.
Rated current (ON current): 0.5 A/output, 4.0 A/common.
Internal I/O common: NPN.
Residual voltage: 1.2 V max. (0 OMRON DRT2-OD32B-1. 5 ADC,
between each output terminal and the G terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Output device supply current: 100 mA/point.
Unit power supply current consumption: 80 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 130 g max.
Expansion functions: No.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common teerminal is provided for,
each connector DRT2-OD32B-1.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software DRT2-OD32B-1.
When setting the nodes with rotary switch,
setting is easy and node identification,