LK Automation Limited LK Automation Limited
Brand: OMRON
Go Back >> Product Catalogues
E5CC-CX2DSM-007 | OMRON Digital temperature controller E5CC-CX2DSM-007
OMRON E5CC-CX2DSM-007 Manual And Instructions
E5CC-CX2DSM-007 datasheetPDF datasheet
E5CC-CX2DSM-007 RS-485 CompoWay/FINSTRUCTION MANUAL
E5CC-CX2DSM-007 Advanced Type
E5CC-CX2DSM-007 User's Manual
E5CC-CX2DSM-007 INSTRUCTION Manual

OMRON E5CC-CX2DSM-007 Product information and technical parameters:
Brand: OMRON
Name: Digital temperature controller
Model: E5CC-CX2DSM-007
Size: 48 x 48mm.
Control output 1: linear current output.
Control output 2:--.
Auxiliary output: 2 independent points.
Power supply voltage: AC/DC24V.
Terminal type: screw terminal table type.
Input category: full range multi input.
Heater break, SSR fault detection function: -.
Communication: -.
Event input: 2 points.
Remote SP input: there.
Transfer output: -.
Using large font PV display (white), improve visibility.
Selection, operation and setting.
Functional performance of input and output points.
Support for more extensive range of applications.
Using high PV 15.2mm display (white), improve visibility.
High speed sampling to achieve 50ms.
With auxiliary output (maximum 3 points), event input (maximum 4 points), the transmission output,
Remote SP input function, support for a variety of applications.
E5CC 60mm has a depth of slender body.
The use of communication adapter cable (sold separately) connected with a computer.
After that, no power supply connection can be set.
It can be easily set by CX-Thermo (sold separately).
Easy to connect with PLC through no program communication.
Combined temperature control device through component communication.

Size: 96 x 96mm.
Category: power AC100 ~ 240V with.
Shell color: black.
Control output 1: position ratio with relay output.
Control output 2: position ratio with relay output.
Control mode: position ratio control.
Auxiliary output points: 2 points.
Event entry point: 2.
Remote SP:4 to 20mA input.
Communication: RS-422 OMRON E5CC-CX2DSM-007.
General thermostat new high performance (high resolution, high speed, high precision input) type products E5CC-CX2DSM-007
Support simple operation, preventive maintenance.
A new type of liquid crystal, which can communicate with the front through the infrared port, is adopted,
Visual angle, contrast can be improved.
High resolution 5 bit display / can display 0.01 degrees C.
High speed sampling period 60ms OMRON E5CC-CX2DSM-007.
All models complete a variety of (to the thermocouple /Pt/ analog input switching), 1 machines to support a variety of sensors.
Also supports remote SP.
Add PV/SV status display function, convenient to check the state of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactive display PV/SV.
By supporting software (Ver.4.0 CX-Thermo) to carry out a simple function (AND/OR logic and delay),
Be able to execute flexible contact output OMRON E5CC-CX2DSM-007.
Increase the control output ON/OFF number counting function, can predict the temperature controller internal relay fault.
Position ratio type. Case color: Black.
Control output: Relay output.
Control mode *1: Standard or heating/cooling.
No. of auxiliary outputs: 2.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: --.
Transfer output *2: --.
Communi cations: --.
Previous model: Thermocouple input, --;
Resistance thermometer input, --.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status off the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV E5CC-CX2DSM-007.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colorrs E5CC-CX2DSM-007.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.


...More relevant models >>>>