LK Automation Limited LK Automation Limited
Brand: OMRON
Go Back >> Product Catalogues
GT1-OD16DS | OMRON Digital I/O Units GT1-OD16DS
OMRON GT1-OD16DS Manual And Instructions
GT1-OD16DS datasheetPDF datasheet
GT1-OD16DS PROGRAMMING MANUAL

OMRON GT1-OD16DS Product information and technical parameters:
Brand: OMRON
Name: Digital I/O Units
Model: GT1-OD16DS
Unit: Connector model.
I/O classification: Digital output.
Internal I/O common: NPN (- common).
I/O points: 16.
I/O connections: D-sub 25-pin connector.
Power supplyvoltage: 24 VDC.
I/O specification: 0.5 A, DC/transistor.
Digital I/O Units Compatible with MULTIPLE I/O TERMINAL,
Terminal block, connector, and high-density connector,
models are available.
The circuit block of the terminal block model can be,
mounted or dismounted for ease of maintenance without,
disconnecting the wires.
DIN track mounting.

Independent type, the function of the built-in controller is not RS-232C, the maximum 256 points.Specifications: I/O; NPN (input: + common,
output: - common); 8 inputs/8 outputs.
I/O connections: Sensor connector.
Rated internal circuit power supply voltage:
Supplied from the communications connector OMRON GT1-OD16DS.
Rated I/O power supply voltage:
Supplied from external source for outputs GT1-OD16DS
Includes Sensor Connector That Conforms to,
Industry Standards And Can Be Used to Connect.
Sensors with Pre-wired Cables without Using,
Special Tools.
Equipped with the standard Smart Slave,
functions that provide powerful.
preventative maintenance and,
troubleshooting capabilities.
Digital I/O Terminal compatible with,
industry-standard sensor connectors OMRON GT1-OD16DS.
Connect sensors easily without special tools.
Reduce time required for wiring.
Load short-circuit detection. Input capacity: 32 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max OMRON GT1-OD16DS.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector GT1-OD16DS.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software GT1-OD16DS.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.


...More relevant models >>>>