I/O classification: Digital I/O.
Internal I/O circuit common: PNP (+ common).
I/O points: 16.
I/O connection method: M3 terminal block.
Added to the Remote I/O Terminal Series.
I/O Points, or Output Points.
connecting to a single wire.
Reduces designing and wiring effort.
Incorporates a removable circuit block of cassette construction.
Input capacity: 32 points.
Rated current (ON current): 0.5 A/output, 4.0 A/common.
Internal I/O common: NPN.
Residual voltage: 1.2 V max. (0.5 ADC,
between each output terminal and the G terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common OMRON SRT2-MD16T-1.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation
SRT2-MD16T-1
I/O power supply method: Supply by I/O power supply.
Output device supply current: 100 mA/point.
Unit power supply current consumption: 100 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 210 g max.
Expansion functions: No OMRON SRT2-MD16T-1.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing OMRON SRT2-MD16T-1.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Input capacity: 16 points.
Rated current (ON current):
0.5 A/output, 4.0 A/common.
Internal I/O common: PNP.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the V terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansionn unit per one I/O terminal unit SRT2-MD16T-1. )
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary sswitch and with tool software SRT2-MD16T-1.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance.